In low voltage three-phase
system there are three single Phases measured between each
phase and a common
point called the “Neutral point”. In actual
fact, the neutral is the common point of three Star-connected windings
where
all three phases meet.
Meaning of Unearthed and Earthed System:
When there is an open circuit between the neutral point and
earth, we say that theNeutral is Unearthed.
On the other hand if there is a connection between
earth And neutral in this case system is called
Earthed.
A directly earthed neutral strongly limits over voltages but it
causes very high fault currents, whereas an
unearthed neutral limits fault
currents to very low values But encourages the occurrence of high over
voltages.
In any installation, service continuity in the event of an
insulation fault is also Directly related to the earthing system. An unearthed neutral
permits service Continuity during an insulation fault. Contrary to this, a
directly earthed neutral, or Low impedance-earthed neutral, causes tripping as soon as
the first insulation fault
Occurs.
However, in an unearthed or high impedance-earthed network, the
damage is Reduced, but the equipment
must have an insulation level
compatible with the level of over voltages able to cope in this type of network. The
choice of earthing system in both low voltage and medium voltage networks depends on the
type of
installation as well as the type of network. It is also influenced
by the type of loads and service continuity
required.
From above discussion it is clear that we have to choose a
compromise between The two, supply continuity and insulation protection.
0 comments:
Post a Comment